Original DATAKOM AVR-8 380V Automatic Voltage Regulator for Generator Alternator: DATAKOM AVR-8 380V voltage regulator is an electronic device that lets the alternator produce a fixed output voltage. Buy Original Datakom AVR-8, Automatic Voltage Regulator, Generator Alternator Online, Buy Generator Engine Parts & Accessories Online

Original DATAKOM AVR-8 380V Automatic Voltage Regulator for Generator Alternator

Quick Details

Place of Origin: Turkey
Brand Name: DATAKOM
Model Number: AVR-8 380V

Packaging & Delivery

Product Description

DATAKOM AVR-8 380V voltage regulator is an electronic device that lets the alternator produce a fixed output voltage. The device has an open chassis, resin moulded design, and is intended to be mounted in the alternator’s terminal box.
The unit does not include moving parts; therefore it is able to operate in highly vibrating environments. The device measures phase to neutral or phase to phase voltage of the alternator and adjusts the DC voltage applied to the excitation winding until reaching the desired voltage.
The unit offers a low-frequency protection feature. A frequency measuring circuit continually monitors the generator output and provides output for low-frequency protection of the excitation system, by reducing the output voltage proportionally with a frequency below a manually adjustable threshold. The nominal frequency can easily be changed to 50 or 60 Hz in the field by push-on link selection.

The sensing loss protection circuit terminates the excitation and protects the windings if there is no voltage on the sensing input. The excitation power is derived directly from the generator terminals. The required minimum residual voltage for build-up is 4 V-AC. The output stage of the device is a Half Wave thyristor output associated with a free-wheeling diode. Basically, the unit is compatible with all brushless type alternators. A stability adjustment potentiometer is also provided for this purpose. A ±3V analogue input is provided allowing external voltage adjustment.

The AVR has the facility for droop CT connection, to allow parallel running with other similarly equipped generators. An overload protection circuit limits the output current to its nominal value, preventing device failure under overload or short circuit conditions.

INSTALLATION

VOLTAGE ADJUSTMENT
The generator output voltage is set at the factory, but can be altered using the VOLT potentiometer or by an external trimmer (if fitted). Terminals T1 and T2 on the AVR will be linked together if no external trimmer is used.

If voltage adjustment is required, proceed as follows:

  1. Before running the generator, turn the VOLT control fully anti-clockwise.
  2. Turn external hand trimmer (if fitted) to the midway position.
  3. Turn STABILITY control to the midway position.
  4. Connect a suitable voltmeter (0-300V ac) across the line to neutral of the generator.
  5. Start the Genset, and run on no load at nominal frequency e.g. 50-53Hz or 60-63Hz.
  6. If the red LED turns on, refer to the Low-Frequency adjustment.
  7. Carefully turn VOLT control clockwise until the rated voltage is reached.
  8. If instability is present at rated voltage, refer to stability adjustment, then re-adjust voltage if necessary.
  9. Voltage adjustment is now completed.
STABILITY ADJUSTMENT

The stability potentiometer adjusts the reaction speed of the device. This helps the unit to comply with various alternators. The correct setting can be found by running the generator at no load and slowly turning the stability control anti-clockwise until the generator voltage starts to become unstable. The optimum or critically damped position is slightly clockwise from this point. The stability selection ‘jumper’ should be correctly linked, A-B, B-C, or A-C at the bottom of the board for the frame size of the generator.

LOW-FREQUENCY PROTECTION ADJUSTMENT

The low-frequency protection circuit shuts off the excitation voltage in order to prevent damage during engine stopping under load. The factory-set value for the protection is 45Hz. Turning the FREQ potentiometer anti-clockwise increases the set value. The red LED indicates that the Under-Frequency-Protection is active.

DROOP ADJUSTMENT

Generators intended for parallel operation are fitted with a quadrature droop Current Transformer(CT). The C.T. is connected to S1, S2 terminals on the AVR. The DROOP adjustment is normally preset in the factory to give a maximum 10% voltage drop at full load. Turning the DROOP potentiometer anti-clockwise decreases the droop voltage.

ANALOGUE ADJUSTMENT

An analogue input (A1 A2) is provided to connect devices that have analogue AVR control output. The input is designed to accept DC signals up to ± 3 volts. The DC signal applied to this input adds to the AVR sensing circuit. A1 is connected to the AVR ground. Positive on A2 increases excitation. Negative on A2 decreases excitation.

TECHNICAL SPECIFICATIONS

SENSING INPUT
1. Voltage:

  • 175-250 V-AC (L-N)
  • 300-435 V-AC (L-L) (see Connection Diagram)

2. Frequency:  50-60 Hz nominal
 POWER INPUT
Voltage:  175-250 V-AC (L-N)
Frequency:  50-60 Hz nominal
OUTPUT  

  • Voltage:  max 90 V-DC at 207 V-AC input
  • Current:  max  8 A-DC (continuous)

REGULATION ± 1% (see note 1)
THERMAL DRIFT 0.03% per °C change in AVR ambient (see note 2)
TYPICAL SYSTEM RESPONSE
AVR response:  20ms
SOFT START 2 sec
EXTERNAL VOLTAGE ADJUSTMENT ±10% with 2 k ohm 1 watt trimmer
UNDER FREQUENCY PROTECTION 42-50 Hz or 52-60 Hz (adjustable)
UNIT POWER DISSIPATION 18 watts maximum
BUILD UP VOLTAGE 4 V-AC at  AVR terminals
ANALOGUE INPUT ±10% with  ±3 V-DC (see note 3)
QUADRATURE DROOP INPUT

  • Max. input:  5A
  • Max. droop: 10% (adjustable)

DIMENSIONS

  • Height: 37mm
  • Weight: 250gr

ENVIRONMENTAL

  • Operating temperature  -20  to +70 °C
  • Maximum humidity  95% non-condensing.
  • Storage temperature  -30 to +80 °C

NOTES 
1. With 4% engine governing.
2. Heated up to 70°C
3. Any device connected to the analogue input must be fully floating (galvanically isolated from the ground), with an insulation strength of 500 V-AC.

WIRING

1.  P: Alternator phase input.
2.  N: Alternator neutral input.
3.  P1, P3: Voltage sensing inputs. (Please refer to Connection Diagram)
4.  T1, T2: External trimmer terminals. Link if not required.
5.  E+, E-: Excitation winding connections.
6.  S1, S2: Droop CT input terminal.
7.  A1, A2: Analogue controller input.
8.  60 HZ:  Link for 60 Hz usage.
9.  A, B, C :

  • Link A-C for under 90KW.
  • Link B-C for 90 ~ 550KW.
  • Link A-B for over 550KW.