Schneider EZC100F3100 Easypact MCCB Circuit Breaker
Characteristics | |
Main | |
Range of product | EasyPact |
Product or component type | Circuit breaker |
Device short name | Easypact EZC100F |
Circuit breaker name | Easypact EZC100F |
Circuit breaker application | Distribution |
Poles description | 3P |
Protected poles description | 3t |
Network type | AC |
DC | |
Network frequency | 50/60 Hz |
[In] rated current | 100 A ( 40 °C ) |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2 |
250 V DC conforming to IEC 60947-2 | |
Breaking capacity code | F |
Breaking capacity | Icu 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Icu 5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 | |
Icu 5 kA at 250 V DC 2P conforming to IEC 60947-2 | |
Icu 5 kA at 125 V DC 1P conforming to IEC 60947-2 | |
Icu 25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 | |
Icu 25 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 | |
Icu 10 kA at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 | |
Icu 10 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Ics] rated service breaking capacity | Ics 3.75 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Ics 2.5 kA 550 V AC 50/60 Hz conforming to IEC 60947-2 | |
Ics 2.5 kA 250 V DC conforming to IEC 60947-2 | |
Ics 2.5 kA 125 V DC conforming to IEC 60947-2 | |
Ics 12.5 kA 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 | |
Ics 12.5 kA 110/130 V AC 50/60 Hz conforming to IEC 60947-2 | |
Ics 5 kA 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
Ics 5 kA 380 V AC 50/60 Hz conforming to IEC 60947-2 | |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Utilisation category | Category A |
Trip unit technology | Thermal-magnetic |
Trip unit rating | 100 A ( 50 °C ) |
Protection type | Overload protection |
Short-circuit protection | |
Pollution degree | 3 conforming to IEC 947-1 |
3 conforming to IEC 60664-1 | |
Complementary | |
Control type | Toggle |
Mounting mode | Fixed |
Mounting support | Backplate |
Upside connection | Front |
Downside connection | Front |
Mechanical durability | 8500 cycles |
Electrical durability | Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 |
Connection pitch | 25 mm |
Local signalling | Positive contact indication |
Neutral protection setting | Without protection |
Earth-leakage protection | Without |
Height | 130 mm |
Width | 75 mm |
Depth | 60 mm |
Environment | |
Standards | GB 14048.2 |
IEC 60947-2 | |
JIS C8201-2-2 | |
NEMA AB1 | |
IP degree of protection | IP20 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -35…85 °C |
Contractual warranty | |
Period | 18 months |